Alarm Configuration in Ericsson System

If a fallback to the previous Ericsson system is necessary during a swap, the alarms must be configured according to the Ericsson system. The 37-pin connector to the Ericsson RBS does not need to be remade during fallback; only the correct alarm cable needs to be punched into the right slot in the Krone block. Grameenphone uses nine alarms identified in their network, which can be supported by both 13-pair and 16-pair alarm cables that use consistent color pairings between cables to identify each alarm type. Taking clear photos of the Krone block configuration before a swap can help avoid confusion during any necessary fallback.

Uploaded by

Reshma Parvin
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
710 views

Alarm Configuration in Ericsson System

If a fallback to the previous Ericsson system is necessary during a swap, the alarms must be configured according to the Ericsson system. The 37-pin connector to the Ericsson RBS does not need to be remade during fallback; only the correct alarm cable needs to be punched into the right slot in the Krone block. Grameenphone uses nine alarms identified in their network, which can be supported by both 13-pair and 16-pair alarm cables that use consistent color pairings between cables to identify each alarm type. Taking clear photos of the Krone block configuration before a swap can help avoid confusion during any necessary fallback.

Uploaded by

Reshma Parvin
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 6

GP ALARM CONFIGURATION IN ERICSSON SYSTEM

If we can not avoid FALLBACK during swap night we have to configure the alarms according to previous system (Ericsson system). At that time alarm configuration may be needed. During the FALLBACK we dont need to remake 37 pin connector which is connected to Ericsson RBS. We just need to punch the alarm cable in Krone Block. The most important thing is that right alarm cable must be punched in right slot of Krone Block.

05/13/12

GRAMEENPHONE LTD.

GP is using nine alarms for its network at present:


Temperature high Mains fail Battery disconnected pre alarm Rectifier module fail Aviation light failure Generator running Fuel level low Water level high Door open

In GP network two types of alarm cables are used:


13 pairs alarm cable 16 pairs alarm cable

05/13/12

GRAMEENPHONE LTD.

13 pairs alarm cable


1st pair: white blue 2nd pair: white orange 3rd pair: white green 4th pair: white brown 5th pair: white gray 6th pair: red blue 7th pair: red orange 8th pair: red green 9th pair: red brown 10th pair: red gray 11th pair: black blue 12th pair: black orange 13th pair: black green Temperature high Mains fail Battery disconnected pre alarm Rectifier module fail Aviation light failure Generator running Fuel level low Water level high Door open N/A N/A N/A N/A

05/13/12

GRAMEENPHONE LTD.

16 pairs alarm cable


1st pair: white blue 2nd pair: white orange 3rd pair: white green 4th pair: white brown 5th pair: white gray 6th pair: red blue 7th pair: red orange 8th pair: red green 9th pair: red brown 10th pair: red gray 11th pair: black blue 12th pair: black orange 13th pair: black green Temperature high Mains fail Battery disconnected pre alarm Rectifier module fail Aviation light failure Generator running Fuel level low Water level high Door open N/A N/A N/A N/A

05/13/12

GRAMEENPHONE LTD.

Basically in both types of alarm cable (13 & 16 pairs) same pair of colors are used for each alarm. For example, in both cases white & blue combination is used for temperature alarm. So we dont need to be bother about the number of pairs of the cable. However, Taking of clear pictures of Krone Block before swap started is also a smart way to avoid confusion during FALLBACK.

05/13/12

GRAMEENPHONE LTD.

05/13/12

GRAMEENPHONE LTD.